Electrical Load Calculator — for Canadian Homes

Calculations use CE Code 2024 Rule 8-200 for single-dwelling service sizing. Verify adopted edition and local amendments with your AHJ.

Loading calculator…

By using this calculator you agree to our Terms. This tool does not provide authoritative or binding interpretations of CSA requirements. All values must be verified by a qualified professional and approved by the Authority Having Jurisdiction (AHJ).

How CEC Rule 8-200 calculates residential demand

Enter living area and connected loads above; the calculator applies Canadian Electrical Code demand factors automatically.

Basic load by floor area

Rule 8-200(1)(a)(i): 5,000 W for the first 90 m² of living area, plus 1,000 W for each additional 90 m² portion. Finished basement area counts at 75% when included.

Heating, cooling, and major appliances

Range, water heater, EV charger, and space-heating loads each follow Rule 8-200 and Section 62 demand rules. HVAC interlocks and individual thermostats adjust heating demand where applicable.

100A vs 200A vs 400A service

Total demand is divided by service voltage to get amps, then compared to standard OCP ratings. Rule 8-200(1)(b) may set a minimum service based on dwelling area.

EV and heat pump impacts

Panel upgrades often trace to EVSE and heat-pump additions. Run scenarios with and without these loads to see service utilization before specifying conductors.

Related free calculators

Four CE Code–aligned tools for Canadian residential work — each runs live in your browser with no signup required for calculations.

Free calculator vs inspection-ready reports

Calculations above are available without an account. Create a free account to save work, export PDFs without watermarks, and unlock multi-dwelling projects.

View pricing

Frequently asked questions

What is a residential electrical load calculator used for?
It estimates service or feeder demand for dwellings using CE Code Rule 8-200 methods so you can support service sizing, panel planning, renovations, and permit documentation alongside your own code review.
How is residential load demand calculated in Canada?
Under Rule 8-200(1)(a), you itemize basic load from floor area, heating and cooling, range, water heating, EV charging, and additional loads over 1,500 W with demand factors. Compare to the Rule 8-200(1)(b) minimum for dwellings 80 m² or larger.
Does this replace Rule 8-200 calculations by hand?
The tool automates structured steps for speed and consistency. You remain responsible for correct inputs and for complying with the adopted code and AHJ requirements.
What service size do I need for my house?
Divide calculated watts by system voltage (typically 240 V single-phase) and round up to standard service ratings: 100 A, 125 A, 200 A, or 400 A. EV chargers, heat pumps, and suites often push upgrades from 100 A to 200 A.
When is 100A service enough in Canada?
100 A (24,000 W at 240 V) satisfies the Rule 8-200(1)(b) minimum for many dwellings 80 m² or larger when itemized load is lower. Smaller homes with modest heat and no large EV loads may remain on 100 A if calculated demand fits.

More Code tools FAQ